Main Article Content

Abstract

In this comprehensive study, we investigated the significant voltage drop observed in the 110 kV high-voltage transmission line connecting the Kajaki Hydroelectric Power Plant to the Kandahar Brishna Kot substation, spanning 171 km. The drop is mainly due to the line’s extended length and its resistive and reactive characteristics. Using both quantitative and qualitative methods, supported by ETAP software and data from Da Afghanistan Breshna Sherkat (DABS), the analysis revealed that the voltage drop exceeds the International Electrotechnical Commission (IEC) standards, resulting in significant power losses. To mitigate this issue, the study recommends upgrading the voltage level from 110 kV to 220 kV. This enhancement would reduce current, minimize resistive losses, and improve efficiency by increasing the conductor's cross-sectional area and reorganizing the transmission route with standard components. Implementing these measures is projected to significantly decrease power losses and enhance the overall reliability and performance of the regional power transmission system.

Keywords

HV Transmission Line Losses Voltage Drop Power Loss Upgrade the Voltage Level Upgrade the Cross-Section Area

Article Details

How to Cite
Rahimi, Q. A., & Sharifi, M. S. (2025). The Power Transmission Losses: Kajaki to Kandahar Breshna Kot. Journal of Natural Sciences – Kabul University, 8(1), 162–143. https://doi.org/10.62810/jns.v8i1.78

References

  1. Abdul Hassan, S. K., & Tuaimah, F. M. (2020). Optimal location of a unified power flow controller genetic algorithm based. International Journal of Power Electronics and Drive System, 11(2), 1-9. https://doi.org/10.11591/ijpeds.v11.i2 DOI: https://doi.org/10.11591/ijpeds.v11.i2.pp886-894
  2. Al-Hinai, M. A., Tanavade, S. S., & Al-Habsi, A. A. (2021). Improving the steady-state stability of 400kv transmission grid using a static synchronous series compensator. International Journal of Electrical Engineering and Technology 12(6), 11. https://doi.org/10.34218/IJEET.12.6.2021.037
  3. Anderson, P. M., & Fouad, A. A. (2003). Power System Control and Stability (Second ed.). JOHN WILEY & SONS. DOI: https://doi.org/10.1109/9780470545577
  4. Da Afghanistan Breshna Sherkat. (2023). Afghanistan South East Power System. Engineering & Technical Studies Deputy, Power System Information Unit. www.aeic.af
  5. Ezechukwu, O. A., & Ogboh, V. C. (2023). Development of ANN Controlled UPFC Based Protection Model for Nigerian 330kv Power Lines. Engineering and Technology Journal, 08(01), 22. https://doi.org/10.47191/etj/v8i1.09, I.F. – 6.484 DOI: https://doi.org/10.47191/etj/v8i1.09
  6. Farzaneh, M., Farokhi, S., & Chisholm, W. A. (2013). Electrical Design of Overhead Power Transmission Lines. McGraw-Hill.
  7. GLOVER, J. D., OVERBYE, T. J., & SARMA, M. S. (2015). POWER SYSTEM ANALYSIS & DESIGN (sixth ed.). CENGAGE Learning.
  8. Hussein, S. A., Mahmood, D. Y., & Numan, A. H. (2023). Loss Reduction of Transmission Lines using PSO-based Optimum Performance of UPFC. Bulletin of Electrical Engineering and Informatics, 12(3), 11. https://doi.org/10.11591/eei.v12i3.4559 DOI: https://doi.org/10.11591/eei.v12i3.4559
  9. Kumar, S. R., & Nagaraju, S. S. (2007). Loss Minimization by Incorporation of UPFC in Load Flow Studies. International Journal of Electrical and Power Engineering, 1(3), 8. https://makhillpublications.co/mak-ijepe/2007/3-321-327
  10. Lakshmana, R., Chowdhury, S. P., Chowdhury, S., Natarajan, A. A., & Gaunt, C. T. (2009). Minimization of Power Loss in Distribution Networks by Different Techniques. International Journal of Electrical Power and Energy Systems Engineering, 2(1), 1-8. https://www.researchgate.net/publication/232607582
  11. Living , O., Nnamchi, S. N., Ukagwu, K. J., AbdulKarim, A., & Jagun, Z. O. (2023). Minimization of Electric Power Losses on 132 kV and 220 kV Uganda Electricity Transmission Lines. Energy and Power Engineering, 15, 1-24. https://doi.org/10.4236/epe.2023.152006 DOI: https://doi.org/10.4236/epe.2023.152006
  12. Llamo-Lahori, H. S., & Santos-Fuentefria, A. (2022). A new method to calculate corona losses for active conductors considering real transmission line unbalance. The Institute of Engineering and Technology, 1-7. https://doi.org/10.1049/tje2.12155 DOI: https://doi.org/10.1049/tje2.12155
  13. MEHTA, V. K., & MEHTA, R. (2008). PRINCIPLE OF POWER SYSTEM (First ed.). New Delhi, India: S. CHAND Company.
  14. Omeje, C. O. (2020). Corona Loss Minimization on High Voltage Transmission Line Network using Bundled Conductors. International Journal of Engineering and Advanced Technology, 9(3), 06. https://doi.org/10.35940/ijeat.C5363.029320 DOI: https://doi.org/10.35940/ijeat.C5363.029320
  15. Pavicic, I., Holjevac, N., Ivankovi´c, I., & Brnobi´c, D. (2021). Model for 400 kV Transmission Line Power Loss Assessment Using the PMU Measurements. Energies, 14, 1-25. https://doi.org/10.3390/en14175562 DOI: https://doi.org/10.3390/en14175562
  16. Rahimi, Q. A. (2023). Analysis and Evaluation of Minimizing Transmission Line Losses Between Kajaki HHPs and Kandahar Breshna Kot Substation. Engineering Faculty, Electrical & Electronics Department, Kabul-Afghanistan.
  17. Sambaiah, K. S., & Jayabarathi, T. (2019). Loss minimization techniques for optimal operation and planning of distribution systems. International Transmission Electrical Energy System, 48. https://doi.org/10.1002/2050-7038.12230 DOI: https://doi.org/10.1002/2050-7038.12230
  18. Singh, E. J. (2018). Real-Time Study on Technical and non-technical Losses in Distribution System and reduction techniques. International journal of innovative research in technology, 5(3), 1-5. https://ijirt.org/publishedpaper/IJIRT147060
  19. SINGH, S. N. (2012). Electric Power Generation, Transmission and Distribution (Second Edition). India, New Delhi-110001: PHI.
  20. Teferra, D. M. (2021). Investigation of Power Flow Effect of Serial and Parallel FACTS Devices. Global Journal of Research and Review, 8(3), 05. https://www.imedpub.com/global-journal-of-research-and-review/
  21. Tuzikova, V., Tlusty, J., & Muller, Z. (2018). A Novel Power Losses Reduction Method Based on a Particle Swarm Optimization Algorithm Using STATCOM. Energies, 15. https://doi.org/10.3390/en11102851 DOI: https://doi.org/10.3390/en11102851
  22. Varghese, J., Sundaramoorthy, K., & Sankaran, A. (2023). Development and Validation of a Load Flow-Based Scheme for Optimum Placing and Quantifying of Distributed Generation for Alleviation of Congestion in Interconnected Power Systems. Energies, 24. https://doi.org/10.3390/en16062536 DOI: https://doi.org/10.3390/en16062536
  23. Woke, A. (2023). Optimization and Reduction of Losses in 330 kV Power System for Efficient and Optimal Operation. International Journal for Research in Applied Science & Engineering Technology, 11(3), 14. https://doi.org/10.22214/ijraset.2023.49163 DOI: https://doi.org/10.22214/ijraset.2023.49163
  24. Wonodi, I., AMADI, H. N., & Blessing Dike, E. (2023). Load Flow Analysis of 132/33 kV Power Network for Voltage Enhancement Using Static VAR Compensation (SVC) Technique. ICONIC RESEARCH AND ENGINEERING JOURNALS, 6(8), 08. https://doi.org/2456-8880